Work on or near energised electrical installations is high-risk construction work. Isolation, proving dead, and a licensed electrician are the job — not a copied “be careful of power” line. If the whole task is an isolated, extra-low-risk fit-off, use the electrical JSA instead.

Generate an electrical SWMSSee live demo

When this is a SWMS — and when it is a JSA

HRCW category: work on or near energised electrical installations or services. Licensed electrician. Isolation and testing are controls, not a reason to skip the SWMS when something in reach is still live.

If the job is an isolated extra-low-risk fit-off — board locked off, proved dead, no live adjacent equipment — use the electrical JSA instead. Don’t dress that JSA up as a live-board SWMS, and don’t downgrade this café upgrade to a JSA because “we’ll try to isolate”.

Filled example: café switchboard, Fortitude Valley QLD

Replace the tenant’s main switchboard. The adjoining tenancy stays open; their supply shares the cupboard. Licensed electrician, isolation of this tenancy, testing, then a controlled restore. Not a new-house GPO fit-off.

Job / task
Replace tenant main switchboard while adjacent tenancy stays energised
Site
Occupied café, Fortitude Valley QLD 4006
Document
SWMS · HRCW: near energised electrical · example only
PPE
Flame-resistant clothing, electrical gloves as the task requires, glasses, steel-caps, isolated tools

Example layout. Residual risk next to a live adjacent board often stays High. Isolated extra-low-risk fit-off: electrical JSA.

StepHazardsControls5×5 risk
1. Permit, identify every source of supply, and agree isolation with the building manager
Responsible: Licensed electrician
  • Unknown backfeed from the café’s generator inlet
  • Adjacent tenancy supply in the same cupboard
  • Café staff walking into the cupboard
  • Trace and label every incoming; lock the generator inlet
  • Written isolation plan; adjacent DB stays covered and treated as live
  • Tape the cupboard; one entry; brief the café manager
InitialL3×C5 = 15 High
ResidualL2×C5 = 10 High
2. Isolate this tenancy, lock-out, prove dead, tag
Responsible: Licensed electrician
  • Wrong isolator — board still live
  • Stored energy in capacitors / UPS under the bench
  • Proving on the wrong circuit
  • Test the tester on a known live, prove dead on the conductors you will touch, re-test the tester
  • Lock and tag; keys with the electrician doing the work
  • Treat the adjacent bus as live for the whole job
InitialL4×C5 = 20 Critical
ResidualL2×C5 = 10 High
3. Remove the old board and terminate the new assembly
Responsible: Licensed electrician
  • Contact with the adjacent live bus in the cupboard
  • Cuts from old DIN gear and sharp enclosure edges
  • Manual handling of the new assembly in a cramped cupboard
  • Insulating covers on the adjacent live parts; no two-handed reach across the live side
  • Isolated tools; glasses; don’t rush terminations
  • Two-person lift into the cupboard; temporary props until the board is fixed
InitialL3×C5 = 15 High
ResidualL2×C5 = 10 High
4. Test, energise under a switching sheet, restore the café
Responsible: Licensed electrician
  • Incorrect polarity or earth before livening
  • Arc on first close if a fault is still on the installation
  • Staff returning to equipment too early
  • Insulation resistance and polarity tests before the main is closed
  • Stand clear on first energisation; switching sheet signed
  • Café manager briefed; no equipment on until the electrician says so
InitialL3×C5 = 15 High
ResidualL2×C5 = 10 High

Frequently asked questions

When do I need an electrical SWMS template?

When the work is on or near energised electrical installations or services — switchboard upgrades with adjacent live tenancies, fault-finding on a live board, any task where isolation of everything in reach is not reasonably practicable. That is HRCW under Schedule 3.

Is the electrical SWMS free to generate?

Trial generate and PDF download, no card. This café board example is a layout. Do not sign it for a different DB.

Do I need a SWMS or a JSA for electrical work?

Energised or near-energised: SWMS. Isolated, proved-dead, extra-low-risk fit-off: JSA is enough for that task. Livening or working next to a live adjacent board puts you back on this page.

Does it cover NSW, VIC, QLD and WA?

Yes — WHS Act/Regulation in NSW, QLD and WA; OHS Act 2004 and OHS Regulations 2017 in Victoria. Electrical licensing and the relevant electrical safety laws in each state still apply on top of the SWMS.

Should residual risk stay High on live electrical work?

Often yes. Isolation cuts likelihood; contact with an adjacent live bus still has severe consequence. Residual High after controls is honest. Residual Low on a live board is not.